Delta CT2000 Series User Manual page 268

Table of Contents

Advertisement

Treatment to 4-20mA Analog Input Signal Loss
Settings
 This parameter determines the behavior when 4~20mA signal is loss, when AVIc(Pr.03-28=2) or
ACIc (03-29=0).
 When Pr.03-28 is not set to 2, it means the voltage input to AVI terminal is 0-10V or 0-20mA. At this
moment, Pr.03-19 will be invalid.
 When Pr.03-29 is set to 1, it means the voltage input to ACI terminal is for 0-10V. At this moment,
Pr.03-19 will be invalid.
 When setting is 1 or 2, it will display warning code "AnL" on the keypad. It will be blinking until the
loss of the ACI signal is recovered or drive is stop.
Multi-function Output 1 (AFM1)
Multi-function Output 2 (AFM2)
Settings
Function Chart
Settings Functions
0
Output frequency (Hz)
1
Frequency command (Hz)
2
Motor speed (Hz)
3
Output current (rms)
4
Output voltage
5
DC Bus Voltage
6
Power factor
7
Power
8
Output torque
9
AVI
10
ACI
11
AUI
12
q-axis current (Iq)
13
q-axis feedback value (Iq)
14
d-axis current (Id)
15
d-axis feedback value (Id)
16
q-axis voltage (Vq)
17
d-axis voltage(Vd)
18
Torque command
Chapter 12 Description of Parameter SettingsCT2000 Series
0: Disable
1: Continue operation at the last frequency
2: Decelerate to stop
3: Stop immediately and display ACE
0~25
Descriptions
Max. frequency Pr.01-00 is regarded as 100%.
Max. frequency Pr.01-00 is regarded as 100%.
600Hz is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2 X rated voltage) is regarded as 100%
450V (900V)=100%
-1.000~1.000=100%
Rated power is regarded as 100%
Full-load torque is regarded as 100%
0~10V=0~100%
0~20mA=0~100%
-10~10V=0~100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
250V (500V) =100%
250V (500V) =100%
Rated torque is regarded as 100%
12.1-03-20
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0