Chapter 11 Summary of Parameter SettingsCT2000 Series
Pr.
Explanation
 10-19
Positioning for Encoder Position
Range for Encoder Position
 10-20
Attained
 10-21
Filter Time (PG2)
10-22
Speed Mode (PG2)
10-23
Reserved
 10-24
FOC&TQC Function Control
FOC Bandwidth of
 10-25
Speed Observer
 10-26
FOC Minimum Stator Frequency
FOC Low-pass Filter Time
 10-27
Constant
FOC Excitation Current Rise
 10-28
Time
 10-29
Top Limit of Frequency Deviation
10-30
Resolver Pole Pair
 10-31
I/F Mode, current command
PM Sensorless Obeserver
 10-32
Bandwidth for High Speed Zone
10-33
Reserved
PM Sensorless Observer
 10-34
Low-pass Filter Gain
 10-35
AMR (Kp)
 10-36
AMR (Ki)
 10-37
PM Sensorless Control Word
10-38
Reserved
Frequency when switch from I/F
 10-39
Mode to PM sensorless mode.
Frequency when switch from PM
 10-40
sensorless observer mode to
V/F mode.
 10-41
I/F mode, low pass-filter time
 10-42
Initial Angle Detection Time
10-43
PG Card Version
10-44
~
Reserved
10-48
 10-49
Zero voltage time while start up
Reverse angle limit (Electrical
 10-50
angle)
 10-51
Injection Frequency
 10-52
Injection Magnitude
PM Motor Initial Rotor Position
 10-53
Detection Method
Settings
-32767~2400
0~65535pulse
0~65.535 sec
0: Electronic Frequency
1: Mechanical Frequency (base on pole pair)
0~65535
20.0~100.0Hz
0.0~2.0%fN
1~1000ms
33~100%Tr
0.00~200.00Hz
1~50
0~150%Irated (Rated current % of the drive)
0.00~600.00Hz
0.00~655.35
0.00~3.00
0.00~3.00
0000~FFFFh
0.00~599.00Hz
0.00~599.00Hz
0.0~6.0sec
0~50ms
0~655.35
00.000~60.000 sec
0.00~30.00 degree
0~1200Hz
0.0~200.0V
0: No functon
1: DC injection
2: High frequency injection
3: Pulse injection
4~5: Reserved
11-36
Factory
Setting
0
10
0.100
0
0
40.0
2.0
50
100
20.00
1
40
5.00
1.00
1.00
0.20
0000
20.00
20.00
0.2
10
Read
only
0.000
10.00
500
15/30
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents