Chapter 12 Description of Parameter SettingsCT2000 Series
AFM2 0-20mA Output Selection
Settings
AFM1 DC output setting level
AFM2 DC Output Setting Level
Settings
Reserved
AFM1 Filter Output Time
Settings
AFM2 Filter Output Time
Settings
~
Reserved
MO by Source of AI Level
Settings
AI Upper Level
Settings
AI Lower Level
Settings
 This function requires to work with Multi-function Output item "67" Analog signal level achieved.
The MO active when AI input level is higher than Pr03-45 AI Upper level. The MO shuts off when
the AI input is lower that Pr03-46 AI Lower level.
 AI Upper level must bigger than AI Lower level.
0: 0-20mA output
1: 4-20mA output
0.00~100.00%
0.00~20.00 sec.
0.00~ 20.00 sec.
0: AVI
1: ACI
2: AUI
-100.00%~100.00%
-100.00%~100.00%
12.1-03-23
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0.01
Factory Setting: 0.01
Factory Setting: 0
Factory Setting:
50.00%
Factory Setting:
10.00%