If this parameter is used without DC brake, it will be invalid. Refer to the following operation timing.
frequ ency
co mma nd
outp ut
frequ ency
RUN/STOP
Mu lti-func tion output
(mec hani cal brake
relea se)
Pr.02-11 to 0 2-14=d12
me chan ical brak e
Output Current Level Setting for Multi-function Output Terminals
Settings
When output current is higher or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 27).
When output current is lower or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 28).
Output Boundary for Multi-function Output Terminals
Settings
When output frequency is higher or equal to Pr.02-34, it will activate the multi-function terminal
(Pr.02-13, 02-14, 02-16, 02-17 is set to 29).
When output frequency is lower
(Pr.02-13, 02-14, 02-16, 02-17 is set to 30).
External Operation Control Selection after Reset and Activate
Settings
Setting 1:
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will
run.
Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
Chapter 12 Description of Parameter SettingsCT2000 Series
ze ro
sp eed
brake
0~100%
0.00~599.00Hz
or equal to
0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
12.1-02-19
A
B=A
RUN
relea se
Pr.02-34, it will activate the multi-function terminal
ze ro
sp eed
STOP
brak e
Tim e
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0