Chapter 12 Description of Parameter SettingsCT2000 Series
 It is used to set the source of the master frequency in HAND mode.
Source of the Operation Command (HAND)
Settings
 It is used to set the source of the operation frequency in HAND mode.
 Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC01 or multi-function input terminal
(MI).
 The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal used
to switch AUTO/HAND mode. The highest priority is the multi-function input terminal. When the
external terminal is OFF, the drive won't receive any operation signal and can't execute JOG.
Digital Keypad STOP Function
Settings
Reserved
~
Homing mode
Settings:
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16 without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication card
4: Reserved
5: Communication card (not include CANopen card
0: STOP key disable
1: STOP key enable
Note: Forward run = clockwise (CW)
Reverse run = counterclockwise (CCW)
12.1-00-16
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0000h