Chapter 12 Description of Parameter SettingsCT2000 Series
It is used to set the source of the master frequency in HAND mode.
Source of the Operation Command (HAND)
Settings
It is used to set the source of the operation frequency in HAND mode.
Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC01 or multi-function input terminal
(MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal used
to switch AUTO/HAND mode. The highest priority is the multi-function input terminal. When the
external terminal is OFF, the drive won't receive any operation signal and can't execute JOG.
Digital Keypad STOP Function
Settings
Reserved
~
Homing mode
Settings:
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16 without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication card
4: Reserved
5: Communication card (not include CANopen card
0: STOP key disable
1: STOP key enable
Note: Forward run = clockwise (CW)
Reverse run = counterclockwise (CCW)
12.1-00-16
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0000h