4. Refer to RTD temperature and resistance comparison table
Temperature=135 , current=151.71
Temperature=150 , current=157.33
5. Set Pr.06=56=1.37 and Pr.06-58=10Hz. When RTD temperature increases to 135
the drive will decelerate to the selected frequency. When Pr.06-58=0, the drive will not run.
6. Set Pr.06-57=1.42 and Pr.06-29=1 (warning and decelerate to stop). When RTD temperature
increases to 150℃ or higher, the drive will decelerate to stop and outputs an 'OH3' warning.
PT100 Activation Level Delay Time
Settings
Software Detection GFF Current Level
Settings
Software Detection GFF Filter Time
Settings
Reserved
Fault Record 1 (day)
Fault Record 2 (day)
Fault Record 3 (day)
Fault Record 4 (day)
Settings
Fault Record 1 (min)
Fault Record 2 (min)
Fault Record 3 (min)
Fault Record 4 (min)
Settings
 When there is any malfunctions in motor drive operation, Pr06-17~22 will record 6 malfunctions
recently, and Pr06-63~70 can record the operation time for 4 malfunctions in sequence. It can help
to check if there is any wrong with the drive according to the recorded internal time.
For example: The first error: ocA occurs in 1000 minutes after motor drive start operation. The
second error: ocd happens after another 1000 minutes. The 4
1000 minutes. Then, the 5
ocn happens 1000 minutes after 5
Then Pr06-17~Pr06-22 and Pr06-63~Pr06-70 will be:
Chapter 12 Description of Parameter SettingsCT2000 Series
; Input current: 9mA, Voltage: approximately: 1.37Vdc
; Input current: 9mA, Voltage: approximately: 1.42Vdc
0~6000 sec.
0.0~6553.5 %
0.00~655.35 sec.
0~65535 day
0~1439 minute
th
error is ocd, happening 1000 minutes following 4
th
error.
12.1-06-19
Factory Setting: 60
Factory Setting: 60.0
Factory Setting: 0.10
Factory Setting: Read only
Factory Setting: Read only
th
error: ocA happens after another
th
error. Last, 6
or higher,
th
error

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents