Mid-point Frequency 1 of Motor 2
Settings
Mid-point Voltage 1 of Motor 2
Settings
Mid-point Frequency 2 of Motor 1
Settings
Mid-point Voltage 2 of Motor 1
Settings
Mid-point Frequency 2 of Motor 2
Settings
Mid-point Voltage 2 of Motor 2
Settings
Min. Output Frequency of Motor 1
Settings
Min. Output Voltage of Motor 1
Settings
Min. Output Frequency of Motor 2
Settings
Min. Output Voltage of Motor 2
Settings
 V/f curve setting is usually set by the motor's allowable loading characteristics. Pay special
attention to the motor's heat dissipation, dynamic balance, and bearing lubricity, if the loading
characteristics exceed the loading limit of the motor.
 There is no limit for the voltage setting, but a high voltage at low frequency may cause motor
damage, overheat, and stall prevention or over-current protection. Therefore, please use the low
voltage at the low frequency to prevent motor damage.
 Pr.01-35 to Pr.01-42 is the V/f curve for the motor 2. When multi-function input terminals
Pr.02-01~02-08 and Pr.02-26 ~Pr.02-31 are set to 14 and enabled, the AC motor drive will act as
the 2nd V/f curve.
Chapter 12 Description of Parameter SettingsCT2000 Series
0.00~599.00Hz
460V series: 0.0~480.0V
0.00~599.00Hz
460V series: 0.0~480.0V
0.00~600.00Hz
460V series: 0.0~480.0V
0.00~599.00Hz
460V series: 0.0~480.0V
0.00~599.00Hz
460V series: 0.0~480.0V
12.1-01-2
Factory Setting: 3.00
Factory Setting: 22.0
Factory Setting: 1.50
Factory Setting: 10.0
Factory Setting: 1.50
Factory Setting: 10.0
Factory Setting: 0.50
Factory Setting: 2.0
Factory Setting: 0.50
Factory Setting: 2.0