Delta CT2000 Series User Manual page 195

Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCT2000 Series
Start-up Display Selection
Settings 0: Display the frequency command (F)
 This parameter determines the start-up display page after power is applied to the drive. User
defined choice display according to the setting in Pr.00-04.
Content of Multi-function Display
Settings 0: Display output current (A)
1: Display the actual output frequency (H)
2: Display User define (U)
3: Output current ( A)
1: Display counter value (c)
2: Display actual output frequency (H.)
3: Display DC-BUS voltage (v)
4: Display output voltage (E)
5: Display output power angle (n)
6: Display output power in kW (P)
7: Display actual motor speed rpm (r = 00: positive speed; -00 negative
speed)
8: Display estimate output torque % (t = 00: positive torque; -00 negative
torque) (t)
9: Display PG feedback (G) (refer to Note 1)
10: Display PID feedback in % (b)
11: Display AVI in % (1.), 0~10V/4-20mA/0-20mA corresponds to 0~100%
(Refer to Note 2)
12: Display ACI in % (2.), 4~20mA/0~10V/0-20mA corresponds to 0~100%
(Refer to Note 2)
13: Display AUI in % (3.), -10V~10V corresponds to -100~100%(Refer to
Note 2)
14: Display the temperature of IGBT in oC (i.)
15: Display the temperature of capacitance in oC (c.)
16: The status of digital input (ON/OFF) refer to Pr.02-12 (i) (Refer to
Note3)
17: Display digital output status ON/OFF (Pr.02-18) (o) (refer to NOTE 4)
18: Display the multi-step speed that is executing (S)
19: The corresponding CPU pin status of digital input (d) (refer to NOTE 3)
20: The corresponding CPU pin status of digital output (0.) (refer to NOTE
4)
12.1-00-2
Factory setting: 0
Factory setting: 3

Hide quick links: