7-6 EMI Filter
The following table shows external EMI filter models for each CT2000 series AC motor drive. Users
can choose corresponding zero phase reactor and applicable shielding cable according to required noise
emission and electromagnetic disturbance rating, to make the best assembly and restrain
electromagnetic disturbance.
CT2000
Frame
Model
VFD110CT43F00B
VFD110CT43A21C
VFD150CT43F00B
B
VFD150CT43A21C
VFD185CT43F00B
VFD185CT43A21C
VFD220CT43F00B
VFD220CT43A21C
VFD300CT43F00B
C
VFD300CT43A21C
VFD370CT43F00B
VFD370CT43A21C
VFD450CT43F00B
VFD450CT43A00C
VFD550CT43F00B
D
VFD550CT43A00C
VFD750CT43F00A6
VFD900CT43F00A8
EMI Filter Installation
All electrical equipment, including AC motor drives, will generate high-frequency/low-frequency noise and will
interfere with peripheral equipment by radiation or conduction when in operation. By using an EMI filter with correct
installation, much interference can be eliminated. It is recommended to use DELTA EMI filter to have the best
interference elimination performance.
We assure that it can comply with following rules when AC motor drive and EMI filter are installed and wired
according to user manual:
EN61000-6-4
EN61800-3: 1996
EN55011 (1991) Class A Group 1 (1
General precaution
1. EMI filter and AC motor drive should be installed on the same metal plate.
2. Please install AC motor drive on footprint EMI filter or install EMI filter as close as possible to the AC motor drive.
3. Please wire as short as possible.
4. Metal plate should be grounded.
5. The cover of EMI filter and AC motor drive or grounding should be fixed on the metal plate and the contact area
should be as large as possible.
Rated
EMI Filter
Amps
(Arms)
25
33
EMF039A43A
40
50
KMF370A
62
79
KMF3100A
91
110
B84143D0200
144
R127
180
st
Environment, restricted distribution)
7-13
Chapter 7 Optional AccessoriesCT2000 Series
CE Cable Length
Zero phase
Default carrier
frequency
reactor
EN61800-3
C2
RF004X00A
100m
RF002X00A
Radiation
Emission
Default carrier
frequency
EN61800-3
C2
100m

Hide quick links: