8-6 EMC-BPS01
External Power
Supply
Note: Refer to I/O & Relay extension card installation/ disconnecting method for PG Card installation/ disconnecting.
Terminals
Input power: 24V±5%
Maximum input current:0.5A
Note:
1) Do not connect control terminal +24V (Digital control signal common:
SOURCE) directly to the EMC-BPS01input terminal 24V.
2) Do not connect control terminal GND directly to the EMC-BPS01 input
terminal GND.
Function: When the drive only power supplied by EMC-BPS01, the
24V
communication works normally, it also can support all communication
GND
cards and the functions mentioned below.
--- Read and Write parameters
--- Keypad can display information
--- Operate keys on the operator panel (except RUN command)
--- Analog input is valid
--- Multi-input (FWD, RV, MI1~MI8) exexute when using external power
Do NOT support:
Relay output (include extension card), PG card, PLC function