Model No.
VFD110CT43A21C
VFD150CT43A21C
VFD185CT43A21C
VFD220CT43A21C
VFD300CT43A21C
VFD370CT43A21C
VFD450CT43A00C
VFD550CT43A00C
VFD750CT43F00A6
VFD900CT43F00A8
The required airflow shown in chart is for installing single drive in a
confined space.
When installing the multiple drives, the required air volume should
be the required air volume for single drive X the number of the
drives.
NOT E
The mounting clearances stated in the figure is for installing the drive in an
open area. To install the drive in a confined space (such as cabinet or
electric box), please follow the following three rules: (1) Keep the minimum
mounting clearances. (2) Install a ventilation equipment or an air
conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr. 00-16, Pr.00-17,
and Pr. 06-55.
The following table shows the heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number the drives.
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Air flow rate for cooling
Flow Rate (cfm)
External Internal Total External Internal Total
134
-
134
134
-
134
134
-
134
173
-
173
173
-
173
173
-
173
202
-
202
202
-
202
-
30
-
-
30
-
Chapter 2 InstallationCT2000 Series
3
Flow Rate (m
/hr)
228
-
228
228
-
228
228
-
228
294
-
294
294
-
294
294
-
294
343
-
343
343
-
343
-
51
-
-
51
-
2-3
Power Dissipation
Power Dissipation
Loss External
Internal
(Heat sink)
177
164
363
194
426
192
523
358
665
363
748
405
906
459
1098
669
1639
657
1787
955
The heat dissipation shown
in the chart is for installing
single drive in a confined
space.
When installing the multiple
drives, volume of heat
dissipation should be the
heat dissipated for single
drive X the number of the
drives.
Heat dissipation for each
model is calculated by
rated voltage, current and
default carrier.
Total
341
557
618
881
1028
1153
1365
1767
2296
2742