Chapter 6 Control TerminalsC2000 Series
Terminals
Multi-function Output 1
MO1
(photocoupler)
Multi-function Output 2
MO2
(photocoupler)
MCM
Multi-function Output Common
Multi-function relay output 1
RA1
Multi-function relay output 1
RB1
Multi-function relay common
RC1
Multi-function relay output 2
RA2
(N.O.) a
Multi-function relay output 2
RB2
(N.C.) b
Multi-function relay common
RC2
+10V
Potentiometer power supply
Potentiometer power supply
-10V
Analog voltage input
AVI
Analog current input
ACI
Auxiliary analog voltage input
AUI
PLC1.ir
Terminal Function
(N.O.) a
(N.C.) b
+10V AVI circuit
AVI
ACM
internal circuit
ACI
ACI circuit
internal circuit
ACM
+10
AU I cir cuit
~
- 10V
AUI
ACM
internal cir cuit
Factory Setting (NPN mode)
The AC motor drive releases various monitor
signals, such as drive in operation, frequency
attained and overload indication, via transistor (open
collector).
Max 48Vdc 50mA
Resistive Load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Inductive Load (COS 0.4):
2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as
drive is in operation, frequency attained or overload
indication.
Analog frequency setting: +10Vdc 20mA
Analog frequency setting: -10Vdc 20mA
Impedance: 20kΩ
Range: 4 ~ 20mA/0~10V =0~Max. Output
Frequency (Pr.01-00)
AVI switch, factory setting is 0~10V
Impedance: 250Ω
Range: 4 ~ 20mA/0~10V= 0 ~ Max. Output
Frequency (Pr.01-00)
ACI Switch, factory setting is 4~20mA
Impedance: 20kΩ
Range: -10~+10VDC=0 ~ Max. Output
Frequency(Pr.01-00)