Analog Input Curve Selection
Settings
AVI Low Point
Settings
AVI Proportional Low Point
Settings
AVI Mid Point
Settings
AVI Proportional Mid Point
Settings
AVI High Point
Settings
AVI Proportional High Point
Settings
When Pr.03-28 = 0, AVI setting is 0-10V and the unit is in voltage (V).
When Pr.03-28 ≠ 0, AVI setting is 0-20mA or 4-20mA and the unit is in current (mA).
When setting analog input AVI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency).
Three of the AVI points can be set according to user's demand on voltage(current) and proportion,
there is no setting limit for ACI points.
Chapter 12 Description of Parameter SettingsCT2000 Series
0: Regular Curve
1: 3 point curve of AVI
2: 3 point curve of ACI
3: 3 point curve of AVI & ACI
4: 3 point curve of AUI
5: 3 point curve of AVI & AUI
6: 3 point curve of ACI & AUI
7: 3 point curve of AVI & ACI & AUI
03-28=0, 0.00~10.00V
03-28≠0, 0.00~20.00mA
-100.00~100.00%
03-28=0, 0.00~10.00V
03-28≠0, 0.00~20.00mA
-100.00~100.00%
03-28=0, 0.00~10.00V
03-28≠0, 0.00~20.00mA
-100.00~100.00%
12.1-03-24
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 5.00
Factory Setting: 50.00
Factory Setting: 10.00
Factory Setting: 100.00