Dc Link Overpower (Error 0X2313/0X161); Pt Power Overload (Error 0X2314/0X162); Uaux Overcurrent (Error 0X2391/0X125); Uaux Overvoltage (Error 0X3292/0X133) - Danfoss VLT MSD 510 Operating Manual

Multiaxis servo drive
Table of Contents

Advertisement

Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
Troubleshooting
Check the servo drive current consumption.
Avoid simultaneous acceleration of all servo drives.
Decrease the acceleration value.

9.2.2.6 DC link Overpower (Error 0x2313/0x161)

This fault applies to the PSM 510.
Possible Causes
The PSM 510 was operating at over 140% of the nominal power rating for too long.
Troubleshooting
Check the current consumption.

9.2.2.7 PT Power Overload (Error 0x2314/0x162)

This fault applies to the PSM 510.
Possible Causes
The PSM 510 was operating at 100–140% of the nominal power rating for too long.
Troubleshooting
Check the current consumption.

9.2.2.8 UAUX Overcurrent (Error 0x2391/0x125)

This fault applies to the DAM 510.
Possible Causes
The servo drives are consuming more power on the U
Troubleshooting
Check the number of attached servo drives with the shell diagrams in the VLT
Design Guide.
Avoid simultaneous lifting of the servo drive brakes.

9.2.2.9 UAUX Overvoltage (Error 0x3292/0x133)

This fault applies to the DAM 510.
Possible Causes
Incorrect U
supply.
AUX
Danfoss A/S © 2019.10
line than allowed.
AUX
®
Servo Drive System ISD 510, DSD 510, MSD 510
Diagnostics
AQ262450196490en-000101 / 175R1170| 169