Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
RCD COMPATIBILITY
The MSD 510 system contains components that can cause a DC current in the protective earthing conductor, which may result
in malfunction in any devices connected to the system.
Where a residual current-operated protective (RCD) or monitoring (RCM) device is used for protection in case of direct or
-
indirect contact, use a type B RCD or RCM device on the supply side of the MSD 510 system components.
All modules must be mounted in a control cabinet.
-
5.3 Grounding
5.3.1 Grounding for Electrical Safety
Illustration 37:
Grounding for Electrical Safety
58 | Danfoss A/S © 2019.10
N O T I C E
N O T I C E
Electrical Installation
AQ262450196490en-000101 / 175R1170