Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
6.14.9 Defining Send Clock and Update Time
6.14.9.1 Configuring the Send Clock Time
Procedure
1. Open the HW Config tool.
2. Select the station with the PROFINET
3. Select the menu [Edit → PROFINET IO → Domain management].
4. In the next window, open the Sync Domain tab and in the Send clock time [ms] field, select an appropriate time for the process, for
example 1.000 ms, then click on OK.
Illustration 94:
126 | Danfoss A/S © 2019.10
®
devices to be involved in IRT communication, for example PNxIO.
Configuring a Send Clock for PROFINET
®
IRT
Commissioning
AQ262450196490en-000101 / 175R1170