Connecting A Monitoring Cable To A Smoke Sensor - Huawei IDS2000 Installation Manual

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Figure 4-207 Connecting a monitoring cable to a door status sensor
Step 2 Assemble the door status sensor by performing steps in
Step 3 Connect the other end of the RJ45 network cable to the AI/DI port on the ECC collector.
----End

4.12.12.12 Connecting a Monitoring Cable to a Smoke Sensor

Prerequisites
A monitoring cable has been prepared as required.
Context
A smoke sensor needs to be connected to the skylight controller.
Procedure
Step 1 Connect the cables for the smoke sensor to the port of the skylight controller as described in
Table
Table 4-17 Cable terminals of the skylight controller
Smoke Sensor Cable
GND (black)
+12 V (red)
Normally open end (blue)
Common end (green)
----End
Issue Draft A (2015-06-29)
4-17.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation
Step 1
in the reverse order.
Skylight Controller Terminal
G-
12 V+
NO
C
171