The server draws in cool air from the front of the cabinet and exhausts hot air
from the rear. Therefore, the front and rear of the cabinet must be well ventilated
for optimal heat dissipation.
Figure 5-3 Direction of heat dissipation

5.4.2 Temperature and Humidity Requirements

To ensure continued safe and reliable equipment operation, install or position the
system in a well-ventilated, climate-controlled environment.
Table 5-2 Temperature and humidity requirements in the equipment room
Item
Temperature
Humidity

5.4.3 Cabinet Requirements

Issue 04 (2020-01-16)
The air conditioning system in the equipment room provides enough wind to
ensure proper heat dissipation of all components.
Use temperature control devices all year long in any climates.
In dry and humid areas, maintain ambient humidity within range with
humidifiers and dehumidifiers respectively.
A standard 19-inch cabinet with a depth of more than 1000 mm (39.37 in.).
Complies with International Electrotechnical Commission 297 (IEC 297).
Copyright © Huawei Technologies Co., Ltd.
Figure 5-3
shows the direction of heat dissipation.
Description
5ºC to 40ºC (41ºF to 104ºF)
8% RH to 90% RH (non-condensing)
5 Install and Configure
44