Setting Network Parameters - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

19.7

Setting Network Parameters

G(P).RLPASET
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions set network parameters in the master station and starts up the data link.
Ladder
(U)
(s1)
(s2)
FBD/LD
EN
ENO
U
d
s1
s2
s3
s4
s5
■Execution condition
Instruction
G.RLPASET
GP.RLPASET
Setting data
■Description, range, data type
Operand
Description
(U)
Start I/O number (first three digits in four-digit
hexadecimal representation) of a module
(s1)
Start device where control data is stored
*2
(s2)
Start device containing the slave station setting data
*2
(s3)
Start device containing the reserved station specification
data
*2
(s4)
Start device containing the error invalid station
specification data
*2
(s5)
Start device containing the automatic update buffer
assignment data
(d)
Device that turns on for one scan upon completion of the
instruction
When the instruction completes with an error, (d)+1 also
turns on.
EN
Execution condition
ENO
Execution result
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
*2 If this operand is omitted, specify the dummy device or label.
RnSFCPU RnSFCPU
(Standard)
(Safety)
(s3)
(s4)
(s5)
(d)
Execution condition
ST
ENO:=G_RLPASET(EN,U,s1,s2,s3,s4,s5,d);
ENO:=GP_RLPASET(EN,U,s1,s2,s3,s4,s5,d);
Range
Data type
00H to FEH
16-bit unsigned binary
Refer to the control data.
Device name
Device name
Device name
Device name
Device name
Bit
Bit
Bit
Data type (label)
ANY16
*1
ANY16
*1
ANY16
*1
ANY16
*1
ANY16
*1
ANY16
ANYBIT_ARRAY
(Number of elements: 2)
BOOL
BOOL
19 CC-LINK INSTRUCTIONS
19.7 Setting Network Parameters
19
1661