For S.2PID (two-degree-of-freedom PID control), set the following operation constant items to specify tracking.
Setting item
Tracking bit (TRK)
Set value pattern (SVPTN)
Loop selector tracking
Tracking processing is performed under the following conditions.
• The control mode is MAN, CMB, CMV, or LCM, and the tracking bit (TRK) is 1.
• The control mode is AUT, CAS, CAB, CCB, CSV, LCA, or LCC, and the tracking bit (TRK) is 1 and BB1 of the block bit (BB)
is 1.
S.IN
(PV1)
(PV2)
S.IN
Ex.
When the input value (E1) of the S.SEL instruction uses the manipulated value (MV) of the upper loop (Loop 0), the
manipulated value (MV) of the S.SEL instruction is tracked to the manipulated value (MV) of Loop 0. The S.SEL instruction
specifies tracking according to the following operation constant items.
...
b15
b5
b4
b3
b2
b1
(s2)+4
1
0
1
0
+5
Operation constant
(s2)+4
Tracking bit
(s2)+5
Set value pattern
Set value pattern
Set value used
Loop tag memory
S.PHPL
S.2PID
Loop 0
Loop 1
S.PHPL
S.2PID
Loop tag memory
b0
1
0
Bit position
b0
b0
b1
b2
b3
b4
Setting
1 (Tracking performed)
0 (Set value is upper loop MV.)
0 (E2 is specified.)
Tracking
S.OUT1
E1
S.SEL
S.OUT1
E2
Stored value
0: Tracking not performed
1: Tracking performed
e1
E1
E2
E1
E2
11 PROCESS CONTROL INSTRUCTIONS
0: E1
1: E2
0: Use
1: Not use
0: Use
1: Not use
0: E1 is the upper loop MV.
1: E1 is not the upper loop
MV.
0: E2 is the upper loop MV.
1: E2 is not the upper loop
MV.
1195
11.1 Overview