Operand: (s1)
Device
Item
+3
Constant link scan time
+4
IP address
+5
*1 If a value outside the setting range is set, the instruction will complete with an error.
*2 If "Invalid" is set, the default parameter will be used.
*3 Set value 121 is available only if the submaster function is used.
For the startup in the local station, only Data link faulty station setting (bit 8 of (s1)+1) and CPU STOP time
output setting (bit 9 of (s1)+1) will be valid. Any other changed settings will be ignored during execution of the
instruction, without causing an error.
■Network configuration setting data (for master station setting only)
Operand: (s2)
Device
Item
+0
For 1st
Slave station
module
setting
information
+1
RX/RY offset
+2
Number of RX/
RY points
+3
RWr/RWw
offset
+4
Number of RWr/
RWw points
+5 to +594
Description
Sets the constant link scan time.
• 0: No operator
• 1 to 200: Constant link scan time
Sets the IPv4 network address (i.e. IP address) when the IP packet transfer function
is used.
(s1)+5
(s1)+4
(s1)+4: Dummy
(s1)+5: Network address
Description
Sets the station type, the number of occupied stations, and the station number.
...
...
b15
b12 b11
(3)
(2)
(1) Station number
• 1 to 120: Station number
• 0: Master station
(2) Number of occupied stations
• 1: Fixed
(3) Station type
• 0: Remote I/O station
• 1: Remote device station
• 2: Intelligent device station
• 3: Local station (master-slave system)
• 4: Submaster station
• F: Master station
Sets the offset value from the head of RX/RY (in units of 16 points).
Sets the number of RX/RY, LB points.
• If the station type is master or local: 0 to 2048 points
• If the station type is intelligent device: 0 to 2048 points (in units of 16 points)
• If the station type is remote I/O: 0 to 64 points (in units of 16 points)
• If the station type is remote device: 0 to 128 points (in units of 16 points)
Sets the offset value from the start of RWr/RWw (in units of 4 points).
Sets the number of RWr/RWw, LW points.
• If the station type is master or local: 0 to 256 points (in units of 16 points)
• If the station type is intelligent device: 0 to 1024 points (in units of 4 points)
• If the station type is remote device: 0 to 64 points (in units of 4 points)
b8 b7
...
(1)
*2
*2
*2
*2
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
*1
Setting range
Set by
0 to 200
User
00000001H to
User
FFFFFFFFH
Setting
Set by
*1
range
Left
User
b0
0 to 16368
User
0 to 2048
User
0 to 64
0 to 128
0 to 8188
User
0 to 256
User
0 to 1024
0 to 64
User
18.7 Setting Parameters
18
1631