■Error invalid station specification data
Operand: (s4)
Device
Item
+0 to +3
Error invalid station
specification
*1 For two or more stations occupied, specify only the slave station start number.
*2 If both the reserved and error invalid stations are specified for the same station, the reserved station specification will take priority.
■Automatic update buffer assignment data
Operand: (s5)
Device
Item
+0 to +77
Automatic update buffer
assignment specification
*1 Beginning at the smallest station number, set the size for the slave stations for which the local or intelligent device station has been set
with the slave station setting data ((s2)+0 to (s2)+63).
*2 The automatic update buffer size must be 1000H (4096) words or less in total. For the automatic update buffer size, specify the required
size for each intelligent device station.
19 CC-LINK INSTRUCTIONS
1664
19.7 Setting Network Parameters
Description
Specifies an error invalid station in a station-by-station manner.
• 0: Not specified
• 1: Specified
b15
b14
b13
(s4)+0
16
15
14
(s4)+1
30
32
31
(s4)+2
48
47
46
(s4)+3
64
63
62
The default value is "0: Not specified" for all stations.
Description
Specifies the assigned buffer memory size (words) that is used for the transient
transmission with the automatic update buffer that is performed to the local or
*1
intelligent device station.
• 0: Not specified
• 1: Specified
(s5)+0
Dummy
(s5)+1
Dummy
Automatic update buffer size
(s5)+2
(s5)+75
Dummy
(s5)+76
Dummy
Automatic update buffer size
(s5)+77
The default value is 0080H.
*1*2
b12
...
b3
b2
b1
13
...
4
3
2
29
...
20
19
18
45
...
36
35
34
61
...
52
51
50
For the 1st module
·
For the 26th module
Setting range
b0
1
17
33
49
Setting range
0H (no setting)
0080H to
*2
1000H
Set by
User
Set by
User