Executing The Protocols Registered For The Predefined Protocol Support Function - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

16.5
Executing the Protocols Registered for the
Predefined Protocol Support Function
GP.ECPRTCL
RnPCPU
RnCPU RnENCPU
(Process)
This instruction executes the communication protocol registered using the engineering tool.
Ladder
(U)
FBD/LD
EN
ENO
U
d
s1
s2
s3
■Execution condition
Instruction
GP.ECPRTCL
Setting data
■Description, range, data type
Operand
Description
(U)
Start I/O number (first three digits in four-digit hexadecimal
representation) of own station or own node
(s1)
Connection No.
(s2)
Number of protocols to be executed continuously
(s3)
Start device of the own station where control data is stored
(d)
Device of the own station, which turns on for one scan
upon completion of the instruction.
When the instruction completes with an error, (d)+1 also
turns on.
EN
Execution condition
ENO
Execution result
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
16 ETHERNET INSTRUCTIONS
1566

16.5 Executing the Protocols Registered for the Predefined Protocol Support Function

RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(s1) (s2)
(s3)
(d)
Execution condition
ST
ENO:=GP_ECPRTCL(EN,U,s1,s2,s3,d);
Range
Data type
00H to FEH
16-bit unsigned binary
1 to 16
16-bit unsigned binary
1 to 8
16-bit unsigned binary
Refer to the control data.
Device name
Bit
Bit
Bit
Data type (label)
ANY16
ANY16
ANY16
*1
ANY16
ANYBIT_ARRAY
(Number of elements: 2)
BOOL
BOOL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents