Calculating The Sine - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

26.6

Calculating the Sine

SIN(_E)
RnPCPU
RnCPU RnENCPU
(Process)
These functions output the sine of an input value.
Ladder, FBD/LD
[Without EN/ENO]
s
d
Setting data
■Description, type, data type
Argument
EN
s (IN)
ENO
d
Processing details
■Operation processing
• These functions calculate the sine of the REAL data type value (angle) input to (s), and output the operation result from (d).
• When the input value is defined as A and the output value is defined as B, the relationship of A and B will be as follows:
B=SIN A
• Input a REAL data type value to (s). Input a value (angle) in radians (angle/180).
■Operation result
1.
Function without EN/ENO
The operation processing is performed. The operation result is output from (d).
2.
Function with EN/ENO
The execution conditions and operation results will be as follows.
Execution condition
EN
TRUE (executed)
FALSE (not executed)
*1 If the value FALSE is output from ENO, the output data from (d) will be undefined. Create a program so that the undefined value will not
be used in operations.
Operation error
Error code
Description
(SD0)
3402H
The input value is -0.
26 SINGLE VARIABLE FUNCTIONS
1900
26.6 Calculating the Sine
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
[With EN/ENO]
EN
ENO
s
Description
Execution condition (TRUE: Executed, FALSE: Not executed)
Input
Output status (TRUE: Normal, FALSE: Abnormal)
Output
Operation result
ENO
TRUE
FALSE
Structured text
[Without EN/ENO]
d:=SIN(s);
[With EN/ENO]
d:=SIN_E(EN,ENO,s);
d
*1
Type
Data type
Input variable
BOOL
Input variable
ANY_REAL
Output variable
BOOL
Output variable
ANY_REAL
(d)
Operation result output value
Undefined value

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents