Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1724

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Control data
Operand: (s)
Device
Item
+0
For system
+1
Execution result
+2
Execution type
+3
CH1 transmission
specifications setting
+4
CH1 communication
protocol setting
+5
CH2 transmission
specifications setting
+6
CH2 communication
protocol setting
+7
Station number setting
+8 to +12
For system
Processing details
• This instruction changes the communication protocol, transmission setting, or station number of each channel of the
module specified by (U).
• The completion status of the ZP.UINI instruction can be checked with the completion device (d) and the completion status
indication device (d)+1.
• Completion device (d)
This device turns on during END processing of the scan where the ZP.UINI instruction completes, and turns off during the next END processing.
• Completion status indication device (d)+1
This device turns on or off depending on the completion status of the ZP.UINI instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the ZP.UINI instruction completes, and turns off during the next
END processing.
• The following figures show how the ZP.UINI instruction operates when its execution completes.
Sequence scan
ZP.UINI instruction
Completion device (d)
Completion status
indication device (d)+1
Mode switching signal
(X6/XD)
Serial
communication
module
20 SERIAL COMMUNICATION INSTRUCTIONS
1722
20.15 Switching the Mode
Description
Always specifies 0.
Used to store the result of sending with the ZP.UINI instruction.
• 0: Normal
• Other than 0: Error (error code)
Specify the execution type.
• 0: Change the settings according to the setting details indicated by (s)+3 and later.
• 1: Restores the setting details of the user parameters that have been set in the
engineering tool.
Sets the CH1 side transmission setting.
Check the current value of the buffer memory area (595 (253H)) to make the settings
identical.
Sets the CH1 side communication protocol.
Check the current value of the buffer memory area (594(252H)) to make the settings
identical.
Sets the CH2 side transmission setting.
Check the current value of the buffer memory area (611(263H)) to make the settings
identical.
Sets the CH2 side communication protocol.
Check the current value of the buffer memory area (610(262H)) to make the settings
identical.
Sets the station number.
Always specifies 0.
0
END
0
Execution of the instruction
OFF
OFF
ON
OFF
END
0
END
0
Set processing
Communications disabled
Setting range
0
0, 1
0 to 4095
(0000H to
0FFFH)
0 to 9
0 to 4095
(0000H to
0FFFH)
0 to 9
0 to 31
0
END
0
END
0
ON
OFF
Completed
ON
with an error
OFF
Completed successfully
1 scan
OFF
Set by
User
System
User
User
User
User
User
User
User
END