■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
*1
(U)
(s1)
(s2)
*2
(d)
*1 Index modification is not available.
*2 FX and FY cannot be used.
*3 RD cannot be used.
*4 FD cannot be used.
*5 T, ST, C, and FD cannot be used.
■Control data
Operand: (s1)
Device
Item
+0
Registration/delete
specification
+1
Registration/delete
result
+2
Frame number
+3
Number of registered
bytes
Processing details
• User frames are registered or deleted for the module specified by (U).
• If a user frame is registered
• To register a user frame, specify 1 for the device of (s1)+0. The data in the device specified by (s2) and later will be registered according to the control data.
• The registered data must be stored as follows in the device specified by (s2) and later. Each of the devices to store the registered data requires the data for
the following number of points from the device specified by (s2): (amount of registered data)/2.
CPU module
...
...
b15
b8
b7
b0
(s2)+0
B
A
(s2)+1
D
C
(s2)+2
F
E
• If a user frame is deleted
• To delete a user frame, specify "3" for the device of (s1)+0. The user frame with the frame number specified by (s1)+2 will be deleted.
• Both the number of registered bytes specified by (s1)+3 and the registered data storage device are required for the G(P).PUTE instruction format although
they are not used by the G(P).PUTE instruction. Specify a value from 1 to 80 for (s1)+3. Specify a dummy device for (s2).
• The completion status of the G(P).PUTE instruction can be checked with the completion device (d) and the completion
status indication device (d)+1.
• Completion device (d)
This device turns on during END processing of the scan where the G(P).PUTE instruction completes, and turns off during the next END processing.
• Completion status indication device (d)+1
This device turns on or off depending on the completion status of the G(P).PUTE instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the G(P).PUTE instruction completes, and turns off during the
next END processing.
Word
J\
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
*3
*4
*4
*5
Description
Specifies whether to register or delete the user frame specified by (s1)+2.
• 1: Registered
• 3: Deleted
Used to store the result of registration or deletion with the G(P).PUTE instruction.
• 0: Normal
• Other than 0: Error (error code)
Specifies the user frame number.
• 1 to 80: Number of bytes of the user frame to be registered
To delete the user frame, specify a value from 1 to 80 as the dummy.
Serial communication
module
User frame
Registering
A
a user frame
B
C
D
E
F
Double word
Indirect
specification
Z
LT, LST,
LZ
LC
(s1)+3
20 SERIAL COMMUNICATION INSTRUCTIONS
20.13 Registering User Frames
Constant
Others
(U)
K, H
E
$
Setting range
Set by
1, 3
User
System
1000 to 1199
User
1 to 80
User
1715
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents