Operand: (s1)
Device
Item
+4
Target network number
+5
Target station number
+6
Not used
+7
Number of resends
15 NETWORK COMMON INSTRUCTIONS
1472
15.1 Link Dedicated Instructions
Description
[CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the network number (1 to 239) of the target station.
[Ethernet]
■When "0" is specified in bit 15 of (s1)+0
Specify the network number (1 to 239) of the target station.
■When "1" is specified in bit 15 of (s1)+0 (Ethernet only)
Specify the IP address (third and fourth octets) of the target station.
...
b15
b8
b7
• b8 to b15: 3rd octet
• b0 to b7: 4th octet
[CC-Link IE Controller Network]
Specify the station number of the target station.
(1) Station number specification
• 1 to 120: Station number
(2) Group number specification
• 0081H to 00A0H: All stations with group numbers 0001H to 0020H
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
(3) All-station specification
• 00FFH: All stations of target network number (broadcast (excluding the own
station))
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
[CC-Link IE Field Network]
Specify the station number of the target station.
(1) Station number specification
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, intelligent device station, submaster station
(2) All-station specification
• 00FFH: All stations of target network number (broadcast (excluding the own
station))
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
[Ethernet]
■When "0" is specified in bit 15 of (s1)+0
Specify the station number of the target station.
(1) Station number specification
• 1 to 120: Station number
(2) Group number specification
• 0081H to 00A0H: All stations with group numbers 0001H to 0020H
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
(3) All-station specification
• 00FFH: All stations of target network number (broadcast (excluding the own
station))
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
■When "1" is specified in bit 15 of (s1)+0
Specify the IP address (first and second octets) of the target station.
...
b15
b8
b7
• b8 to b15: 1st octet
• b0 to b7: 2nd octet
Effective when the execution type specified by (s1) is "1: Arrival acknowledgment
used".
■Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
• 0 to 15 (times)
■At completion of instruction
The number of resends performed (result) is stored.
• 0 to 15 (times)
...
b0
...
b0
Setting range
Set by
■(s1)+4
User
Network No.:
1 to 239
■(s1)+5
Station No.:
1 to 120, 125, 126
Group number:
0081H to 00A0H
All-station
specification:
00FFH
■(s1)+4, 5
IP address:
User
00000001H to
FFFFFFFEH
(1 to 4294967294)
0 to 15
User/
system