Starting a block

SET [BL]
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
• The RnCPU and RnENCPU with firmware version "12" or later support this instruction. (Use an engineering tool with version "1.015R" or later.)
• The RnPCPU (process) with firmware version "03" or later supports these instructions. (Use an engineering tool with version "1.020W" or later.)
This instruction activates the specified block, and executes a step sequence starting from an initial step.
Ladder
(d)
FBD/LD
EN
ENO
d
■Execution condition
Instruction
SET
Setting data
■Description, range, data type
Operand
Description
(d)
Block No. to be activated
(Set (on) target bit device number)
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, S,
SB, FX, FY
(d)
*1 The BL can be index modified.
Processing details
• This instruction activates the specified block, and executes a step sequence starting from an initial step. When there are
several initial steps, all the initial steps are activated.
• If the block start/end bit of the SFC information device is set, the corresponding bit device turns on.
• If the instruction is executed to an active block, the instruction is ignored and processing will continue.
• If the instruction is executed to an inactive block for which online change is being performed, the instruction is ignored and
processing will continue.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=SET(EN,d);
Range
Data type
Bit
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
13 SFC PROGRAM INSTRUCTIONS
Data type (label)
ANY_BOOL
BOOL
BOOL
Constant
Others
specification
(BL)
K, H E
$
13.1 SFC Control Instructions
13
*1
1425