Setting data
■Description, range, data type
Operand
Description
(J)
Target network number
(s1)
Channel of the own station, which is used for the
instruction
(s2)
Target station number
(s3)
Start I/O number of target station
(s4)
Start address of the buffer memory area of the
intelligent device station or the remote device station
to which the data is written
(s5)
Start device of the own station, where the write-
target data is stored
(n)
Number of write data points (in units of words)
(d)
Device of the own station, which turns on for one
scan upon completion of the instruction.
When the instruction completes with an error, (d)+1
also turns on.
EN
Execution condition
ENO
Execution result
*1 A channel is used only for the REMFR, REMTO, REMFRD, and REMTOD instructions.
The same channel number used for the link dedicated instructions (such as the READ instruction) can be set.
*2 This is the start I/O number (first three digits in four-digit hexadecimal representation) of intelligent function modules.
*3 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
*4 When a station in a redundant system is targeted, specify the station number in the control system by using the module FB
(RedundantSystem_GetAddress).
 MELSEC iQ-R Ethernet/CC-Link IE Function Block Reference
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B,
SB, FX, FY
(J)
*1
(s1)
*1
(s2)
*1
(s3)
*1
(s4)
(s5)
*1
(n)
*1
(d)
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
1616
18.4 Writing Data to the Intelligent Device Station/Remote Device Station (32-bit Address Specified)
*1
*4
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
*2
*2
*2
*2
*2
*2
*3
Range
1 to 239
1 to 32
1 to 120
■Head module:
*2
00H to FEH
■Modules other than the head
module:
00H (fixed)
0000H to FFFFFFFFH (0 to
4294967295)
1 to 240
Double word
U\G, J\,
Z LT, LST,
U3E\(H)G
LC
 
 
 
 
 
 
 
 
Data type
Data type (label)
16-bit unsigned binary
ANY16
16-bit unsigned binary
ANY16
16-bit unsigned binary
ANY16
16-bit unsigned binary
ANY16
32-bit unsigned binary
ANY32
Device name
ANY16
16-bit unsigned binary
ANY16
Bit
ANYBIT_ARRAY
(Number of elements:
2)
Bit
BOOL
Bit
BOOL
Indirect
Constant
specification
LZ
K, H E $
*3
Others
(J)
  
  
  
  
  
  
  
  