Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1629

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

: Supported, : Not supported
Device
Bit
Item
1st word
b0 to b3
Reserved
b4 to b7
Module type
*3
b8 to b10
Series
b11 to b15
Reserved
2nd word
b0 to b1
Error status
b2
Module ready
*3
status
b3 to b5
Reserved
b6 to b7
Inter-module
synchronization
b8 to b9
Reserved
b10
External power
*3
supply
*3
b11
Fuse
b12
Reserved
b13
Online module
change
b14
Reserved
b15
Module access
*2
Description
Fixed to 0
*3
0000:Input module, or not set (default)
0010:Output module
0100:I/O combined module (different numbers)
0110:I/O combined module (same number)
1000:Intelligent function module
Further details can be checked in b0 to b3 of the 3rd
word.
000: (default)
010:MELSEC-Q series module
011:MELSEC iQ-R series module
111:Unknown
Fixed to 0
*3
00: No error (default)
01: Minor error
10: Moderate error
11: Major error
0: Not ready (default)
1: Ready
Fixed to 0
00: Not synchronized (default)
*3
01: Preparing for synchronization
10: Synchronized
11: Synchronization error
Fixed to 0
0: Normal operation (default)
1: Power off
0: Normal operation (default)
1: Fuse blown
Fixed to 0
0: Not being performed (default)
1: Module being changed online
Fixed to 0
0: Disabled (default)
1: Enabled
18.6 Reading the Module Status Information of an Intelligent Device Station
Power
Base
supply
unit
module
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
Modules
mounted on the
CPU slot and
slot No.0 to
No.63
18
*4
1627