Operand: (s1)
Device
Item
+11
Clock setting flag
+12
Clock data
(Set only in an
abnormal state)
+13
+14
+15
+16
Error detection network
number
+17
Error-detected station
number
■Request data
Operand: (s2)
Device
Item
+0
Not used
+1
Command
+2
Subcommand
+3 to +
SLMP frame data
*1 For details on the SLMP frame, refer to the following.
 SLMP Reference Manual
■Response data
Operand: (d1)
Device
Item
+0
End code
+1 to +
Response data
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
1640
18.9 Sending an SLMP Frame
Description
The validity status (valid or invalid) of the data in (s1)+12 and later is stored.
Note that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Year (00H to 99H: Lower two digits of the year)
Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
The network number of the station in which an error was detected is stored.
• 1 to 239 (Network number)
The number of the station where an error was detected is stored.
• 1 to 120: Local station, intelligent device station, remote device station,
submaster station
• 125: Master station
• 126: Master operating station
Description
Sets the command of the SLMP frame.
Sets the subcommand of the SLMP frame.
Stores the SLMP frame data after the subcommand.
Description
Stores the result of command processing.
In normal end, 0 is stored. In abnormal end, an error code set by the external
device is stored.
Sets execution results for the request data.
(Some commands do not return response data.)
*1
*1
*1
Setting range
Set by
System
System
System
System
System
System
System
Setting range
Set by
Refer to the
User
manual of the
User
target station.
User
Setting range
Set by
System
System

Hide quick links: