Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1741

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• For R60AD16-G
Operand: (s)
Device
Item
+0
System area
+1
Completion status
+2
Save data type setting
+3
System area
+4
CH1 Factory default setting offset value (L)
+5
CH1 Factory default setting offset value (H)
+6
CH1 Factory default setting gain value (L)
+7
CH1 Factory default setting gain value (H)
+8
CH2 Factory default setting offset value (L)
+9
CH2 Factory default setting offset value (H)
+10
CH2 Factory default setting gain value (L)
+11
CH2 Factory default setting gain value (H)
+12
CH3 Factory default setting offset value (L)
+13
CH3 Factory default setting offset value (H)
+14
CH3 Factory default setting gain value (L)
+15
CH3 Factory default setting gain value (H)
+16
CH4 Factory default setting offset value (L)
+17
CH4 Factory default setting offset value (H)
+18
CH4 Factory default setting gain value (L)
+19
CH4 Factory default setting gain value (H)
+20
CH5 Factory default setting offset value (L)
+21
CH5 Factory default setting offset value (H)
+22
CH5 Factory default setting gain value (L)
+23
CH5 Factory default setting gain value (H)
+24
CH6 Factory default setting offset value (L)
+25
CH6 Factory default setting offset value (H)
+26
CH6 Factory default setting gain value (L)
+27
CH6 Factory default setting gain value (H)
+28
CH7 Factory default setting offset value (L)
+29
CH7 Factory default setting offset value (H)
+30
CH7 Factory default setting gain value (L)
+31
CH7 Factory default setting gain value (H)
+32
CH8 Factory default setting offset value (L)
+33
CH8 Factory default setting offset value (H)
+34
CH8 Factory default setting gain value (L)
+35
CH8 Factory default setting gain value (H)
+36
CH9 Factory default setting offset value (L)
+37
CH9 Factory default setting offset value (H)
+38
CH9 Factory default setting gain value (L)
+39
CH9 Factory default setting gain value (H)
+40
CH10 Factory default setting offset value (L)
+41
CH10 Factory default setting offset value (H)
+42
CH10 Factory default setting gain value (L)
+43
CH10 Factory default setting gain value (H)
+44
CH11 Factory default setting offset value (L)
Description
The instruction completion status is stored.
• 0: Completed successfully
• Other than 0: Completed with an error (error code)
Specifies which one of the voltage and current is read as the
offset/gain setting value.
• 0: Voltage specification
• 1: Current specification
b15
b14
b13
b12
b11
b10
b9
b8
b7
CH
CH
CH
CH
CH
CH
CH
CH9
CH8
CH7
16
15
14
13
12
11
10
Setting range
0000H to FFFFH
b6
b5
b4
b3
b2 b1 b0
CH6
CH5
CH4
CH3 CH2 CH1
21 A/D CONVERSION INSTRUCTIONS
21.2 Reading the User Range Setting Values
Set by
System
User
System
System
21
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
1739