■Block memory
Operand: (d1)
Device
Symbol
Name
+0
BW
Output value
+1
+2
BB
BB1
Data sufficiency
bit
■Operation constant
Operand: (s2)
Device
Symbol
Name
+0
ST
Data sampling
+1
interval
+2
SN
Sampling count
■Local work memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
Operand: (d2)
Position
Symbol
Name
+0
ST'
Last data
+1
sampling
interval
+2
SN'
Last sampling
count
+3
i
Cycle counter
+4
n1
Number of data
blocks stored
+5
n2
Storage address
+6
+7
+8
1
Dead time table
+9
1
+10
2
Dead time table
+11
2
+2SN+6
SN
Dead time table
+2SN+7
SN
*1 The cycle counter value is rounded off to the nearest whole number.
■Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
Recommended range
-999999 to 999999
...
b15
0: Data sufficient
1: Data insufficient
Recommended range
0 to 999999 [s]
Set a value within the following range.
ST
<=32767
©T
0 to 48
Recommended range
*1
Data type
Single-precision
real number
Unsigned
b0
16-bit binary
data
Data type
Single-precision
real number
16-bit unsigned
binary
Data type
Single-precision
real number
16-bit unsigned
binary
16-bit unsigned
binary
16-bit unsigned
binary
16-bit unsigned
binary
Single-precision
real number
11 PROCESS CONTROL INSTRUCTIONS
11.4 Correction Operation Instructions
Standard
Set by
value
System
System
11
Standard
Set by
value
1.0
User
0
User
Standard
Set by
value
System
System
System
System
System
System
1357