Converting Dword To Int - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

25.15

Converting DWORD to INT

DWORD_TO_INT(_E)
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These functions convert a value from DWORD data type to INT data type.
Ladder, FBD/LD
[Without EN/ENO]
s
d
Setting data
■Description, type, data type
Argument
Description
EN
Execution condition (TRUE: Executed, FALSE: Not executed)
s (IN)
Input
ENO
Output status (TRUE: Normal, FALSE: Abnormal)
d
Output
Processing details
■Operation processing
• These functions convert the value input to (s) from DWORD data type to INT data type, and output the converted value
from (d).
• The upper 16-bit data of the input value (DWORD data type) are discarded. (Refer to (1) in the figure below.)
(s)
BC614EH
DWORD
BC614EH
0 0 0 0 0 0 0 0 1 0 1 1 1 1 0 0
24910
(1)
• Input a DWORD data type value to (s).
■Operation result
1.
Function without EN/ENO
The operation processing is performed. The operation result is output from (d).
2.
Function with EN/ENO
The execution conditions and operation results will be as follows.
Execution condition
EN
TRUE (executed)
FALSE (not executed)
*1 If the value FALSE is output from ENO, the output data from (d) will be undefined. Create a program so that the undefined value will not
be used in operations.
RnSFCPU RnSFCPU
(Standard)
(Safety)
[With EN/ENO]
EN
ENO
s
d
0
1
1
0
0
0
0
1
0
1
1
0
0
0
0
1
Operation result
ENO
TRUE
*1
FALSE
Structured text
[Without EN/ENO]
d:=DWORD_TO_INT(s);
[With EN/ENO]
d:=DWORD_TO_INT_E(EN,ENO,s);
Type
Input variable
Input variable
Output variable
Output variable
(d)
24910
INT
0
1
0
0
1
1
1
0
0
1
0
0
1
1
1
0
(d)
Operation result output value
Undefined value