Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1584

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Description, range, data type
Operand
Description
(J/U)
J(P).RSTOP
(J): Target station network number
G(P).RSTOP
(U): Start I/O number (first three digits in four-digit hexadecimal
representation) of own station or own node
Z(P).RSTOP
(J): Target station network number
Z(P).RSTOP
(U): Start I/O number (first three digits in four-digit hexadecimal
representation) of own station or own node
(s1)
Own station channel ( Page 1450 Range of available
channel numbers)
(s2)
Specify the station number of the target station/target node.
(1) Station number specification
1 to 120
(2) Group specification
81H to A0H: All stations of group numbers 1 to 32
(3) All-station specification
FFH: All stations of target network numbers, except own
station
(s3)
Specify that CPU module in the target station that is to be
accessed.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
(s4)
Specifies the operation mode. (0001H (fixed))
(d)
Device of the own station, which turns on for one scan upon
completion of the instruction.
When the instruction completes with an error, (d)+1 also turns
on.
EN
Execution condition
ENO
Execution result
*1 If the instruction is executed with group or all stations specification:
For the target station CPU type, specify either 0000H or 03FFH. If the target station is in CC-Link IE Field Network, group specification is
not available. To check that the data has been written successfully in the target station, examine whether the CPU module of the
destination has entered the STOP state.
*2 If the instruction is executed with the control system CPU (03D0H) or standby system CPU (03D1H) specified, it may complete with an
error if system switching occurs in the target station (error code: 4244H, 4248H).
Retry to execute the instruction if it completed with an error due to the above error.
• Remote STOP is enabled when the RUN/STOP/RESET switch of the target station CPU module is "RUN."
• If the target station CPU module is system protected, remote STOP will fail.
• Resetting the target station CPU on which remote STOP was executed deletes information about the
remote STOP.
17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
1582
17.2 Remote STOP
*1
*1
*2
*2
Range
Data type
1 to 239
16-bit unsigned binary
00H to FEH
16-bit unsigned binary
1 to 239
String
00H to FEH
String
1 to 8, 11 to 18
16-bit unsigned binary
1 to 120
16-bit unsigned binary
81H to A0H
FFH
0000H
16-bit unsigned binary
03D0H to 03D3H
03E0H to 03E3H
03FFH
0001H (fixed)
16-bit unsigned binary
Bit
Bit
Bit
Data type (label)
ANY16
ANY16
ANY16_OR_STRING_
SINGLE
ANY16_OR_STRING_
SINGLE
ANY16
ANY16
ANY16
ANY16
ANYBIT_ARRAY
(Number of elements: 2)
BOOL
BOOL

Hide quick links: