■Input data
Operand: (s1)
Position
Symbol
Name
+0
E1
Input value
+1
■Block memory
Operand: (d1)
Position
Symbol
Name
+0
BW
Output value
+1
+2
BB
BB1
Alarm
BB2
Large deviation
alarm
BB3
Output upper
limit alarm
BB4
Output lower
limit alarm
BB5
Output variation
rate alarm
■Operation constant
Operand: (s2)
Position
Symbol
Name
+0
MTD
Derivative gain
+1
+2
DVLS
Large deviation
+3
alarm hysteresis
+4
PN
Operation mode
+5
TRK
Tracking bit
+6
SVPTN
Set value
pattern
+7
NMAX
Output
+8
conversion
upper limit
+9
NMIN
Output
+10
conversion
lower limit
Recommended range
-999999 to 999999 [%]
Recommended range
-999999 to 999999
...
b15
b4
0: No alarm
1: Alarm
Recommended range
0 to 999999
0 to 100 [%]
0: Reverse action
1: Direct action
0: Tracking not performed
1: Tracking performed
0 to 3
...
b15
(1) Use of set value
Specify whether to use the set value (E2) or not.
0: Used
1: Not used
(2) Set value pattern
Specify whether to use the upper loop MV as the set value (E2) or
not.
0: E2 is the upper loop MV.
1: E2 is not the upper loop MV.
-999999 to 999999
-999999 to 999999
Data type
Single-precision
real number
Data type
Single-precision
real number
16-bit unsigned
b3 b2 b1
b0
binary
Data type
Single-precision
real number
Single-precision
real number
16-bit unsigned
binary
16-bit unsigned
binary
16-bit unsigned
binary
b0
(2)
(1)
Single-precision
real number
Single-precision
real number
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
Standard
Set by
value
User
11
Standard
Set by
value
System
System
Standard
Set by
value
8.0
User
2.0
User
0
User
0
User
3
User
100.0
User
0.0
User
1247