Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1763

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• For R60DA16-G
Operand: (s)
Device
Item
+0
System area
+1
Completion status
+2
Save data type setting 1
+3
Save data type setting 2
+4
CH1 Factory default setting offset value
+5
CH1 Factory default setting gain value
+6
CH2 Factory default setting offset value
+7
CH2 Factory default setting gain value
+8
CH3 Factory default setting offset value
+9
CH3 Factory default setting gain value
+10
CH4 Factory default setting offset value
+11
CH4 Factory default setting gain value
+12
CH5 Factory default setting offset value
+13
CH5 Factory default setting gain value
+14
CH6 Factory default setting offset value
+15
CH6 Factory default setting gain value
+16
CH7 Factory default setting offset value
+17
CH7 Factory default setting gain value
+18
CH8 Factory default setting offset value
+19
CH8 Factory default setting gain value
+20
CH9 Factory default setting offset value
+21
CH9 Factory default setting gain value
+22
CH10 Factory default setting offset value
+23
CH10 Factory default setting gain value
+24
CH11 Factory default setting offset value
+25
CH11 Factory default setting gain value
+26
CH12 Factory default setting offset value
+27
CH12 Factory default setting gain value
+28
CH13 Factory default setting offset value
+29
CH13 Factory default setting gain value
+30
CH14 Factory default setting offset value
+31
CH14 Factory default setting gain value
+32
CH15 Factory default setting offset value
+33
CH15 Factory default setting gain value
+34
CH16 Factory default setting offset value
+35
CH16 Factory default setting gain value
+36
CH1 User range setting offset value
+37
CH1 User range setting gain value
+38
CH2 User range setting offset value
Description
The instruction completion status is stored.
• 0: Completed successfully
• Other than 0: Completed with an error (error code)
Used to store the set value that was set for Save data type
setting 1 (s)+2 in the G(P).OGLOAD instruction.
• 0H: User range setting 1 (current specification)
• 1H: User range setting 2 (voltage specification)
• 2H: User range setting 3 (voltage specification)
b15
b14
b13
b12
b11
b10
b9
b8
b7
CH8
CH7
CH6
CH5
CH4
Used to store the set value that was set for Save data type
setting 2 (s)+3 in the G(P).OGLOAD instruction.
• 0H: User range setting 1 (current specification)
• 1H: User range setting 2 (voltage specification)
• 2H: User range setting 3 (voltage specification)
b15
b14
b13
b12
b11
b10
b9
b8
b7
CH16
CH15
CH14
CH13
CH12
Setting range
0000H to
AAAAH
b6
b5
b4
b3
b2 b1 b0
CH3
CH2
CH1
0000H to
AAAAH
b6
b5
b4
b3
b2 b1 b0
CH11
CH10
CH9
21 A/D CONVERSION INSTRUCTIONS
21.3 Restoring the User Range Setting Values
Set by
System
System
System
21
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
System
1761

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents