■Loop stop processing (6)
The following processing is performed according to the SPA status of the alarm detection (ALM).
SPA status
1
0
■Control cycle determination (7)
If the specified control cycle is not reached, BW (MV) is set to 0 and the S.PID instruction is terminated.
If the specified control cycle is reached, "SV setting processing (1)" is performed.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
The value specified by (s1), (s2), or (d2) is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
3405H
The control cycle (CT) setting is less than 0.
The execution cycle (T) setting is less than 0.
The value divided the control cycle (CT) by the execution cycle (T) exceeds 32767.
11 PROCESS CONTROL INSTRUCTIONS
1238
11.3 Control Operation Instructions
Processing details
The loop stops. When the loop stops, the following operations are performed and the S.PID instruction ends.
• The output value (BW (MV)) is set to 0.
• The DVLA of alarm detection (ALM) is set to 0.
• The control mode (MODE) is set to MAN.
• BB1 of BB is set to 0.
The loop runs and "control cycle determination processing (7)" is performed.