Setting data
■Description, range, data type
Operand
Description
(J/U)
J(P).RTMWR
(J): Target station network number
G(P).RTMWR
(U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own node
Z(P).RTMWR
(J): Target station network number
Z(P).RTMWR
(U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own node
(s1)
Own station channel ( Page 1450 Range of available
channel numbers)
(s2)
Specify the station number of the target station/target node.
(1) Station number specification
1 to 120
(2) Group specification
81H to A0H: All stations of group numbers 1 to 32
(3) All-station specification
FFH: All stations of target network numbers, except own
station
(s3)
Specify that CPU module in the target station that is to be
accessed.
(s4)
Own station start device containing the clock data to be written
(d)
Device of the own station, which turns on for one scan upon
completion of the instruction.
When the instruction completes with an error, (d)+1 also turns
on.
EN
Execution condition
ENO
Execution result
*1 If the instruction is executed with group or all stations specification:
For the target station CPU type, specify either 0000H or 03FFH. If the target station is in CC-Link IE Field Network, group specification is
not available. To check that the data has been written successfully in the target station, examine whether the CPU module of the
destination has entered the RUN state.
*2 If the instruction is executed with the control system CPU (03D0H) or standby system CPU (03D1H) specified, it may complete with an
error if system switching occurs in the target station (error code: 4244H, 4248H).
Retry to execute the instruction if it completed with an error due to the above error.
17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
1592
17.4 Writing Clock Data to the Programmable Controller on Another Station
*1
*1
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
Range
1 to 239
00H to FEH
1 to 239
00H to FEH
1 to 8, 11 to 18
1 to 120
81H to A0H
FFH
0000H
03D0H to 03D3H
03E0H to 03E3H
*2
03FFH
*2
Data type
Data type (label)
16-bit unsigned binary
ANY16
16-bit unsigned binary
ANY16
String
ANY16_OR_STRING_
SINGLE
String
ANY16_OR_STRING_
SINGLE
16-bit unsigned binary
ANY16
16-bit unsigned binary
ANY16
16-bit unsigned binary
ANY16
Device name
ANY16_ARRAY
(Number of elements: 5)
Bit
ANYBIT_ARRAY
(Number of elements: 2)
Bit
BOOL
Bit
BOOL