Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1284

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Block memory
Operand: (d1)
Position
Symbol
+0
BW
+1
+2
BB
BB1
BB2
BB3
BB4
BB5
■Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
Operand: (d2)
Position
Symbol
+1
MODE
+3
ALM
+4
INH
+10
PV
+11
+22
RH
+23
+24
RL
+25
+26
PH
+27
+28
PL
+29
+30
HH
+31
+32
LL
+33
11 PROCESS CONTROL INSTRUCTIONS
1282
11.3 Control Operation Instructions
Name
Recommended range
Output value
-999999 to 999999 [%]
Alarm
b15
Upper limit
alarm
Lower limit
alarm
0: No alarm
1: Alarm
Positive
direction
variation rate
alarm
Negative
direction
variation rate
alarm
Name
Recommended range
Control mode
0 to FFFFH
...
b15
Alarm detection
0 to FFFFH
b15 b14
SPA
0: Loop RUN
1: Loop STOP
HHA, LLA, PHA, PLA, DPPA, DPNA
0: No alarm
1: Alarm
Disable alarm
0 to FFFFH
detection
...
b15
0: Alarm detection enabled
1: Alarm detection disabled
Process value
RL to RH
Engineering
-999999 to 999999
value upper limit
Engineering
-999999 to 999999
value lower limit
Upper limit
RL to RH
alarm value
Lower limit
RL to RH
alarm value
Upper upper
RL to RH
limit alarm value
Lower lower limit
RL to RH
alarm value
...
b4
b3 b2 b1
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
...
...
b8 b7 b6 b5
b4
b3
...
b8 b7 b6 b5 b4 b3
Data type
Single-precision
real number
16-bit unsigned
b0
binary
Data type
16-bit unsigned
binary
b0
16-bit unsigned
binary
b0
16-bit unsigned
binary
b0
Single-precision
real number
Single-precision
real number
Single-precision
real number
Single-precision
real number
Single-precision
real number
Single-precision
real number
Single-precision
real number
Standard
Set by
value
System
System
Standard
Set by
value
8H
User/
system
4000H
User/
system
4000H
User/
system
0.0
System
100.0
User
0.0
User
100.0
User
0.0
User
100.0
User
0.0
User

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents