Reading Receive Data (For Interrupt Programs) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Reading receive data (for interrupt programs)

G.BUFRCVS, Z.BUFRCVS
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions read receive data from the external device through fixed buffer communications (for interrupt programs).
Ladder
(U)
(s)
(d)
FBD/LD
EN
ENO
U
d
s
■Execution condition
Instruction
G.BUFRCVS
Z.BUFRCVS
Setting data
■Description, range, data type
Operand
Description
(U)
GP.BUFRCVS
Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own
node
ZP.BUFRCVS
Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own
node
(s)
Connection No.
(d)
Own station start device for storing the receive data
EN
Execution condition
ENO
Execution result
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B,
SB, FX, FY
(U)
GP.BUFRCVS
ZP.BUFRCVS
*1
(s)
(d)
*1 FX and FY cannot be used.
*2 FD cannot be used.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
J\
T, ST, C, D, W,
U\G, J\,
SD, SW, FD,
U3E\(H)G
R, ZR, RD
*2
*2
ST
ENO:=G_BUFRCVS(EN,U,s,d);
ENO:=Z_BUFRCVS(EN,U,s,d);
Range
Data type
00H to FEH
16-bit unsigned binary
00H to FEH
String
1 to 16
16-bit unsigned binary
Device name
Bit
Bit
Double word
Indirect
specification
Z
LT, LST,
LZ
LC
16 ETHERNET INSTRUCTIONS
16.3 Fixed Buffer Communications Instructions
16
Data type (label)
ANY16
ANY16_OR_STRING
_SINGLE
ANY16
*1
ANY16
BOOL
BOOL
Constant
Others
(U)
K, H
E
$
1557

Hide quick links:

Advertisement

Table of Contents
loading