■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B,
SB, FX, FY
(J/U)
J(P).RSTOP
G(P).RSTOP
Z(P).RSTOP
*1
(s1)
*1
(s2)
*1
(s3)
*1
(s4)
*1
(d)
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
Processing details
• Remote STOP is executed for the target station CPU module. The target station is specified with the target network number
(J) or the start I/O number (U) of the own station or node and the target station number (s2). After completion of request to
the target station, the completion device specified by (d) turns on.
[Own station]
CPU module
(s4)
RSTOP
CH: Channel
• The specifiable stations are those with the specified network number that are included in one of the following networks.
• MELSECNET/H
• MELSECNET/10
• CC-Link IE Controller Network
• CC-Link IE Field Network
• Ethernet
• The execution status and the completion status of the RSTOP instruction can be checked with the completion device (d)
and the completion status indication device (d)+1.
• Completion device (d)
This device turns on during END processing of the scan where the RSTOP instruction completes, and turns off during the next END processing.
• Completion status indication device (d)+1
This device turns on or off depending on the completion status of the RSTOP instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the RSTOP instruction completes, and turns off during the next
END processing.
Word
J\
T, ST, C, D, W,
U\G, J\,
SD, SW, FD,
U3E\(H)G
R, ZR, RD
*2
*2
*2
*2
*3
CC-Link IE Controller
Network module
CH1
CHn
CH8
Double word
Indirect
specification
Z
LT, LST,
LZ
LC
[Target station]
CPU module
STOP
17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
Constant
Others
K, H
E
$
J
U
Network module
1583
17.2 Remote STOP
17