Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1356

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Block memory
Operand: (d1)
Device
Symbol
+0
BW
+1
■Operation constant
Operand: (s2)
Device
Symbol
+0
SN
■Local work memory
Operand: (d2)
Position
Symbol
+0
X1
+1
+2
Y1
+3
+4
X2
+5
+6
Y2
+7
+4SN-4
Xn
+4SN-3
+4SN-2
Yn
+4SN-1
Processing details
This instruction outputs values according to the inverse function generator pattern consisting of n break points as specified by
(s2) with regard to the input value (E1).
Y
E1
(X
, Y
)
1
1
BW
The S.IFG instruction performs the following operations.
Condition
E1Y1
Y
<E1Y
(i=2 to n)
i-1
i
Y
<E1
n
• If the value specified in (n) is 0, no processing is performed.
• If X
> X
, processing is stopped when n = i - 1. (The subsequent data is ignored.)
i - 1
i
• When there are two or more X
11 PROCESS CONTROL INSTRUCTIONS
1354
11.4 Correction Operation Instructions
Name
Recommended range
Output value
-999999 to 999999
Name
Recommended range
Number of break
0 to 48
points
Name
Recommended range
Break point
-999999 to 999999
coordinates
Break point
coordinates
Break point
coordinates
Break point
coordinates
Break point
coordinates
Break point
coordinates
(X
, Y
)
3
3
(X
, Y
)
2
2
for the same Y
i
(X
, Y
)
4
4
X
Output value (BW)
BW=X1
X
-X
i
i-1
BW=
×(E1-Y
)+X
i-1
i-1
Y
-Y
i
i-1
BW=X
n
, the X with smaller i is selected.
i
Data type
Standard
Set by
value
Single-precision
System
real number
Data type
Standard
Set by
value
16-bit unsigned
0
User
binary
Data type
Standard
Set by
value
Single-precision
User
real number

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents