■Control data
Operand: (s1)
Device
Item
+0
Execution/error
completion type
+1
Completion status
+2
Own station channel
+3
Target station CPU type
Description
...
b15
b8
b7
(4)
0
(3) (2)
(1) Execution type (b0)
• 0: No arrival acknowledgment
When the target station is in the same network: Completed when data has been sent
from the own station.
Request
Target
source
station
Completed
When the target station is in another network: Completed when data has arrived the
relay station of the own network.
Request
Relay
source
station
Completed
• 1: Arrival acknowledgment used
Sending data is completed when the data is written to the target station.
Request
Relay
source
station
Completed
Target
station
(2) Error completion type (bit 7)
Specify whether to set clock data when completed with an error.
• 0: Do not set data in (s1)+11 and later at completion with an error.
• 1: Set data in (s1)+11 and later at completion with an error.
(3) Arrival check time setting (bit 8)
• 0: 1s units
• 1: 100ms units
(4) Target station address specification method (b15)
• 0: Specify "network No." in (s1)+4, and "station number" in (s1)+5.
• 1: Specify the IP address in (s1)+4, 5 (Ethernet only)
The completion status is stored upon completion of the instruction.
• 0: Normal
• Other than 0: Error (error code)
Specify the channel to be used by own station. (Page 1450 Range of available
channel numbers)
Specify the CPU type of the target station.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
...
b0
0
(1)
Target
station
Completed
Target
station
15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
Setting range
Set by
0000H
User
0001H
0080H
0081H
0100H
0101H
0180H
0181H
8000H
8001H
8080H
8081H
8100H
8101H
8180H
8181H
System
1 to 18
User
0000H
User
03D0H to 03D3H
03E0H to 03E3H
03FFH
1479
15