Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1686

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• The following figure shows how the G(P).OUTPUT instruction operates when completing its execution.
Sequence scan
G(P).OUTPUT instruction
Completion device (d)
Completion status
indication device (d)+1
Precautions
• The following table summarizes the processes that take place if another instruction is issued while the G(P).OUTPUT
instruction is active or the G(P).OUTPUT instruction is issued while another instruction is active with the same channel.
Instruction to execute
*2
concurrently
G(P).OUTPUT
G.INPUT
G(P).PRR
ZP.CSET
G(P).PUTE
G(P).GETE
Z.BUFRCVS
G(P).SPBUSY
ZP.UINI
*2 The following instructions are not available with the same channel as for the G(P).OUTPUT instruction because they use a
communication protocol different from the one used by this instruction. In addition, if these are used with the same channel as for the
G(P).OUTPUT instruction, a communication protocol setting error (7FF2H) will occur.
• G(P).ONDEMAND, G(P).CPRTCL, G(P).BIDOUT, and G(P).BIDIN instructions
• The local device and the file register for each program are not available for setting data.
Operation error
Error code
Description
((s1)+1)
 MELSEC iQ-R Serial Communication Module User's Manual (Application)
7000H to 7FFFH
20 SERIAL COMMUNICATION INSTRUCTIONS
1684
20.3 Sending Data Using the Nonprocedural Protocol
0
END
0
Execution of the instruction
OFF
OFF
Possibility of
concurrent execution
END
0
END
Completion of
the instruction
Handling for concurrent execution
The instruction is ignored and does not start processing until the active instruction
completes.
Concurrent execution is, however, possible if they use different channels.
A dedicated instruction concurrent execution error (7FF0H) occurs in the second
instruction.
Concurrent execution is, however, possible if they use different channels.
A dedicated instruction concurrent execution error (7FF0H) occurs in the second
instruction.
0
END
0
ON
OFF
Completed with an error
ON
OFF
Completed successfully
1 scan
END

Hide quick links: