Chapter 14 Redundant System Instructions; System Switching - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

14
REDUNDANT SYSTEM INSTRUCTIONS
14.1

System Switching

SP.CONTSW
RnPCPU
RnCPU RnENCPU
(Process)
This instruction switches the systems (control system and standby system) during END processing of the scan where the
instruction is executed.
Ladder
(s)
FBD/LD
EN
ENO
s
d
■Execution condition
Instruction
SP.CONTSW
Setting data
■Description, range, data type
Operand
Description
(s)
Instruction ID number:
A value used to identify a system switching request
(d)
Error completion device:
The device turns on when the system switching operation
failed.
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(s)
(d)
14 REDUNDANT SYSTEM INSTRUCTIONS
1440
14.1 System Switching
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(d)
Execution condition
Word
J\
T, ST, C, D, W,
SD, SW, FD,
R, ZR, RD
ST
ENO:=SP_CONTSW(EN,s,d);
Range
-32768 to 32767
Double word
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Data type
Data type (label)
16-bit signed binary
ANY16
Bit
ANY_BOOL
Bit
BOOL
Bit
BOOL
Indirect
Constant
specification
LZ
K, H
Others
E
$