■Block memory
Operand: (d1)
Device
Symbol
Name
+0
BW
Output value
+1
+2
BB
BB1
Upper limit
alarm
BB2
Lower limit
alarm
■Operation constant
Operand: (s2)
Device
Symbol
Name
+0
HILMT
Upper limit
*1
+1
value
+2
LOLMT
Lower limit
*1
+3
value
+4
HS1
Upper limit
+5
hysteresis
+6
HS2
Lower limit
+7
hysteresis
*1 Set the upper limit (HILMT) and lower limit values (LOLMT) in such a way that HILMT equals to or exceeds LOLMT.
Processing details
This instruction applies upper and lower limiters with hysteresis to the output value.
HILMT
HILMT-HS1
LOLMT
LOLMT+HS2
BB1
BB2
The S.LIMT instruction performs the following operations.
Condition
E1HILMT
(LOLMT+HS2)<E1<(HILMT-HS1)
E1LOLMT
Other than the above (hysteresis part)
Recommended range
-999999 to 999999 [%]
...
b15
0: No alarm
1: Alarm
Recommended range
-999999 to 999999 [%]
-999999 to 999999 [%]
0 to 999999 [%]
0 to 999999 [%]
BW
HILMT-HS1
HILIMT
LOLMT+HS2
LOLMT
Data type
Single-precision
real number
16-bit unsigned
b1 b0
binary
Data type
Single-precision
real number
Single-precision
real number
Single-precision
real number
Single-precision
real number
X1
BW
BB1
HILMT
1
E1
0
LOLMT
0
E1
Last value
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
Standard
Set by
value
System
System
11
Standard
Set by
value
100.0
User
0.0
User
0.0
User
0.0
User
BB2
0
0
1
Last value
1309