Precautions
• In a simultaneous sequence, specify and activate all the steps by using the SET instruction (Activating a step). If there is
any inactive step left, a convergence is not performed. Likewise, if the RST instruction (Deactivating a step) is executed to
a single step in a simultaneous sequence, a convergence condition is not satisfied.
• The current step No. cannot be specified within the action of the SFC program. If specified, an error occurs.
Operation error
Error code
Description
(SD0)
31A1H
The specified block does not exist. (SET/RST BL\S)
31A2H
When a block No. is specified, the specified block No. is out of the range, 0 to 319.
31B1H
The instruction is executed when no SFC program (scan execution type) exists or SM321 is off.
No specified step exists in the specified block. (SET/RST BL\S/S)
31B2H
The specified step No. is out of the range, 0 to 511.
31B5H
The current step is specified within the action.
13 SFC PROGRAM INSTRUCTIONS
1436
13.1 SFC Control Instructions