■Input data
Operand: (s1)
Device
Symbol
Name
+0
E1
Input value
+1
+2
e1
Operation
control signal
■Block memory
Operand: (d1)
Device
Symbol
Name
+0
BW
Output value
+1
■Operation constant
Operand: (s2)
Device
Symbol
Name
+0
T
Derivative time
+1
+2
Ys
Output initial
+3
value
■Local work memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
Operand: (d2)
Position
Symbol
Name
+0
E1
Last input value
n-1
+1
■Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
Processing details
This instruction performs differentiation operation according to the operation control signal (e1).
E1
t
The S.D instruction performs the following operations.
e1
BW
0
T
BW=
T+© T
However, BW = 0 when T+T = 0.
1
BW=Ys
E1: Input value of this time, T: Execution cycle, E1
Recommended range
-999999 to 999999
...
b15
0: Differentiation operation performed
1: Differentiation operation not performed
Recommended range
-999999 to 999999
Recommended range
0 to 999999 [s]
-999999 to 999999
Recommended range
BW
TS
1+TS
×(Y
-E1
+E1)
n-1
n-1
: Last input value, Y
n-1
Data type
Single-precision
real number
16-bit unsigned
b0
binary
Data type
Single-precision
real number
Data type
Single-precision
real number
Single-precision
real number
Data type
Single-precision
real number
t
: Last output value
n-1
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
Standard
Set by
value
User
User
11
Standard
Set by
value
System
Standard
Set by
value
1.0
User
0.0
User
Standard
Set by
value
System
1293