Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1595

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B,
SB, FX, FY
(J/U)
J(P).RTMWR
G(P).RTMWR
Z(P).RTMWR
*1
(s1)
*1
(s2)
*1
(s3)
(s4)
*1
(d)
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■Clock data
Operand: (s4)
Device
Item
Description
+0
Change pattern
Specifies the bit pattern that indicates the item of the clock data to be changed.
• 0: Not changed
• 1: Changed
b15
b7: Year (first two digits), b6: Day of week, b5: Second, b4: Minute, b3: Hour, b2:
Day, b1: Month, b0: Year (last two digits)
+1
Clock data
Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Month (01H to 12H)
The range of the 4 digits of the year is 1980 to 2079.
+2
Upper 8 bits: Day (01H to 31H)
Lower 8 bits: Hour (00H to 23H)
+3
Upper 8 bits: Minute (00H to 59H)
Lower 8 bits: Second (00H to 59H)
+4
Upper 8 bits: Year (19H and 20H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
The range of the 4 digits of the year is 1980 to 2079.
If the target station CPU module is system protected, writing the clock data will fail.
Word
J\
T, ST, C, D, W,
U\G, J\,
SD, SW, FD,
U3E\(H)G
R, ZR, RD
*2
*2
*2
*2
*3
...
b8
b7
b6
b5
b4
b3
0
17.4 Writing Clock Data to the Programmable Controller on Another Station
Double word
Indirect
specification
Z
LT, LST,
LZ
LC
b2
b1
b0
17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
Constant
Others
K, H
E
$
J
U
Setting range
Set by
0, 1
User
Year: 00H to 99H
User
Month: 01H to 12H
Day: 01H to 31H
User
Hour: 00H to 23H
Minute: 00H to 59H
User
Second: 00H to 59H
Year: 19H to 20H
User
Day of week: 00H to 06H
1593